PTK-HF signal cable

Application

PTK-HF halogen free signal cables are used as tele, fire, theft and alarm cable in low voltage systems. For indoor use, solid hem. The cable must not be walled or buried in the ground.

Construction

Conductor

Copper threads (Ø. 0.6 mm)

Insulation

PE (Ø. 1.0 mm)

Conductor color

Red, blue, yellow, white, green, black

Filling sheath

HFFR

Outer sheath

Halogen free, white

Technical data

Working temperature

-30° C to +70° C

Test voltage

1500 V

Bend radius

7.5 x cable diameter

Technical comments

Conductor resistance (max.): 65 Ohm/km.
Insulation resistance (min.): 2 GOhm/km. 
Capacitance (@ 800 Hz): 55nF/km.

CPR classification:
Please request for DoP at dop@scankab.dk

Approvals

IEC 60332-1, IEC 61034-2, IEC 60754-2, CE, RoHS
Bending radius 7,5 x cable diameter
Can lay in tubes
Environmentally friendly
Flame retardant acc. to IEC 60332-1
For use in homes
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Low smoke emission during fire acc. to 61034
Max. working temp. +70° C
Min. working temperature -30° C
Suited for public places
SKU EAN CPR Dimension (mm) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
407040006 5704403050932 - 4x0,60 - D./Cut 3,5 10,4
407040006D 5704403050932 Dca 4x0,60 - D./Cut 3,5 10,4
407060006 5704403048489 - 6x0,60 - T-500 4,2 15,6
407060006D 5704403048489 Dca 6x0,60 - T-500 4,2 15,6
407080006 5704403051687 - 8x0,60 - D./Cut 4,5 20,8
407080006D 5704403051687 Dca 8x0,60 - D./Cut 4,5 20,8
407100006 5704403051694 - 10x0,60 - D./Cut 5,0 26,0
407120006 5704403051700 - 12x0,60 - D./Cut 5,4 31,2
407120006D 5704403051700 Dca 12x0,60 - D./Cut 5,4 31,2
* The values can have small deviations