Medium Voltage aluminium cable PEX-AL-CT for the transport and distribution networks, power plants, transformer units, connection between overhead lines and transformers. This cable can be installed in ducts, direct buried or in the open air.
Aluminium, class 2 acc. to IEC 60228
Cross-linked polyethylene type DIX 12 according to HD 620-1
Black with white numbering,
Strippable screen over the insulation, made of thermosetting semiconductor material.
Metallic screen with longitudinal water tightness made of a concentric layer of copper wires with one helically wound copper
tape over hygroscopic tape helically.
Polyethylene type DMP 13 according to HD 620-1, red
-15° C to +90° C
12 kV
15 x cable diameter
Short circuit temp.: max 250° C / 5 sec.
SKU | EAN | Dimension (mm2) | Current Value (A) | Winding | Diameter (mm)* | Weight (kg/km)* | |
---|---|---|---|---|---|---|---|
963150003 | 5704403207138 | 3x150/25 | 309 | Drum | 57,7 | 2715 | |
963240003 | 5704403207145 | 3x240/35 | 415 | Drum | 67,3 | 3885 | |
963300003 | 5704403207275 | 3x300/35 | 475 | Drum | 72,8 | 4765 | |
* The values can have small deviations |