NA2XS(FL)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.
Alu-threads, class 2
Extruded semi-conducting layer around the conductor
XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape
Cu threads and Cu counter helix over tape material
Water blocking tape
Polyethylene DMP2, black
Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness
-20° C to +90° C
6/10 kV (12 kV) (Uo/U (Um))
15 x cable diameter
SKU | EAN | Dimension (mm2) | Current Value (A) | Winding | Diameter (mm)* | Weight (kg/km)* | |
---|---|---|---|---|---|---|---|
10201185.DE | 5704403205240 | 1x185/25 | 424 | Drum | 32,4 | 1320 | |
10201240.DE | 5704403205257 | 1x240/25 | 502 | Drum | 34,9 | 1540 | |
10201300.DE | 5704403205264 | 1x300/25 | 577 | Drum | 36,9 | 1725 | |
* The values can have small deviations |