X-VOLT ® NA2XS(FL)2Y, (3x) - 6/10 (12) kV

Application

NA2XS(FL)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Construction

Conductor

Alu-threads, class 2
Extruded semi-conducting layer around the conductor

Insulation

XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape

Screen

Cu threads and Cu counter helix over tape material
Water blocking tape

Outer sheath

Polyethylene DMP2, black

Comments

Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness

Technical data

Working temperature

-20° C to +90° C

Rated voltage

6/10 kV (12 kV) (Uo/U (Um))

Bend radius

15 x cable diameter

Approvals

HD 620-1, IEC 60502-2, IEC 60228, IEC 60754-1/2, CE, RoHS
Abrasion resistant
Bending radius 15 x cable diameter
Can be buried
Can be immersed into water
Can lay in tubes
Low emission of corrosive gases acc. to IEC 60754
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -20° C
Outdoor use
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
1013T185.DE 5704403205271 3x1x185/25 424 Drum 69,5 4000
1013T240.DE 5704403205288 3x1x240/25 502 Drum 74,9 4660
1013T300.DE 5704403205295 3x1x300/25 577 Drum 79,2 5225
* The values can have small deviations