NA2XSY single, AL - 6/10 (12) kV

Application

NA2XSY is used for installations indoor as well as outdoor, above or directly in the ground, in tubes or water.

Construction

Conductor

Round alu-threads, class 2
Semi conducting layer around the conductor

Insulation

XLPE insulated
Semi conducting layer around the insulation

Filling sheath

Tape of conductive material

Screen

Cu threads over tape material

Outer sheath

PVC, red

Technical data

Working temperature

-5° C to +90° C

Rated voltage

6/10 kV (12 kV)

Test voltage

21 kV

Bend radius

15 x cable diameter

Approvals

IEC 60502, IEC 60332-1-2, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
Flame retardant acc. to IEC 60332-1
For use in wind turbines
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -5° C
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
871011392 - 1X50/16 183 Drum 25 780
871011393 - 1X70/16 228 Drum 27 870
871012614 - 1X70/35 228 Drum 27 1395
871011394 - 1X95/16 278 Drum 28 990
871011395 - 1X120/16 321 Drum 30 1100
871012615 - 1X120/50 321 Drum 30 1659
871011396 5704403172788 1X150/16 364 Drum 31 1250
871011397 - 1X150/25 364 Drum 31 1300
871011398 - 1X185/16 418 Drum 33 1400
871011399 - 1X185/25 418 Drum 33 1450
871011400 - 1X240/16 494 Drum 35 1600
871011401 - 1X240/25 494 Drum 35 1650
871011402 - 1X300/25 568 Drum 37 1950
871011403 - 1X400/35 660 Drum 41 2350
871011404 - 1X500/35 767 Drum 44 2700
871014005 - 1X630/35 - Drum 44 2996
* The values can have small deviations