NA2XS2Y single, Cu - 18/30 (36) kV

Application

NA2XS2Y is used for installations indoor as well as outdoor, above or directly in the ground, in tubes or water.

Construction

Conductor

Round alu-threads, class 2
Semi conducting layer around the conductor

Insulation

XLPE insulated
Semi conducting layer around the insulation

Filling sheath

Tape of conductive material

Screen

Cu threads over tape material

Outer sheath

PE, black

Technical data

Working temperature

-20° C to +90° C

Rated voltage

18/30 kV (36 kV)

Test voltage

63 kV

Bend radius

15 x cable diameter

Approvals

IEC 60502, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
For use in wind turbines
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -20° C
UV-resistant
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
871011453 - 1X50/16 187 Drum 34 1100
871011454 - 1X70/16 232 Drum 36 1200
871011455 - 1X95/16 282 Drum 37 1300
871011456 - 1X120/16 325 Drum 39 1450
871011457 - 1X150/25 367 Drum 40 1650
871011458 - 1X185/25 421 Drum 42 1800
871011459 - 1X240/25 496 Drum 44 2050
871011460 - 1X300/25 568 Drum 47 2300
871011461 - 1X400/35 659 Drum 50 2750
871011462 - 1X500/35 764 Drum 53 3150
871013116 - 1X630/35 890 Drum 62 3770
* The values can have small deviations