N2XS(F)2Y - 6/10 (12) kV

Application

N2XS(F)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.

Construction

Conductor

Bare stranded Cu, class 2
Extruded semi-conducting layer around the conductor

Insulation

XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape

Screen

Cu threads and Cu counter helix over tape material
Water blocking tape

Outer sheath

Polyethylene DMP2, black

Comments

Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness

Technical data

Working temperature

-20° C to +90° C

Rated voltage

6/10 kV (12 kV)

Test voltage

21 kV

Bend radius

15 x cable diameter

Approvals

VDE 0276-620, CE, RoHS
Bending radius 15 x cable diameter
Can be buried
Can be immersed into water
Can lay in tubes
Max. working temp. +90° C
Medium voltage cable
Min. working temperature -20° C
Outdoor use
SKU EAN Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
871013261 - 1X35/16 197 Drum 24 820
871011479 - 1X50/16 236 Drum 25 1150
871011480 - 1X70/16 294 Drum 27 1400
871011481 - 1X95/16 358 Drum 28 1650
871011482 - 1X120/16 413 Drum 30 1900
871011483 - 1X150/25 468 Drum 31 2300
871011484 - 1X185/25 535 Drum 33 2650
871011485 - 1X240/25 631 Drum 35 3250
871011486 5704403160471 1X300/25 722 Drum 37 3850
871011487 - 1X400/35 827 Drum 41 4800
871011488 - 1X500/35 949 Drum 44 5900
871012224 - 1X630/35 1090 Drum 49 7014
871014387 - 1X800/35 - Drum 57 8800
* The values can have small deviations