N2XS(F)2Y is used for installation in ground, in water, outdoors, indoors and in cable ducts for power stations, industry, and distribution networks. The high mechanical durability of the PE-sheath permits strong mechanical stress during installation or during operation. The water blocking tape avoids water propagation inside the cable.
Bare stranded Cu, class 2
Extruded semi-conducting layer around the conductor
XLPE DIX8
Extruded semi-conducting layer around the insulation
Semi-conducting water blocking tape
Cu threads and Cu counter helix over tape material
Water blocking tape
Polyethylene DMP2, black
Laminated sheath
Polymer laminated aluminum tape 0.25 mm
PE-sheath
Cross and longitudinal watertightness
-20° C to +90° C
18/30 kV (36 kV)
63 kV
15 x cable diameter
SKU | EAN | Dimension (mm2) | Current Value (A) | Winding | Diameter (mm)* | Weight (kg/km)* | |
---|---|---|---|---|---|---|---|
871011516 | - | 1X50/16 | 241 | Drum | 34 | 1650 | |
871011517 | - | 1X70/16 | 299 | Drum | 36 | 1900 | |
871011526 | 5704403174805 | 1X95/16 | 363 | Drum | 37 | 2150 | |
871011519 | - | 1X120/16 | 4118 | Drum | 39 | 2450 | |
871011520 | - | 1X150/25 | 472 | Drum | 40 | 2750 | |
871011521 | - | 1X185/25 | 539 | Drum | 42 | 3150 | |
871011972 | - | 1X185/35 | 539 | Drum | 42 | 2955 | |
871011522 | - | 1X240/25 | 635 | Drum | 44 | 3800 | |
871012216 | - | 1X240/70 | 539 | Drum | 44 | 3786 | |
871011523 | - | 1X300/25 | 725 | Drum | 47 | 4400 | |
871011524 | - | 1X400/35 | 831 | Drum | 50 | 5450 | |
871011525 | - | 1X500/35 | 953 | Drum | 53 | 6550 | |
871012226 | - | 1X630/35 | 1094 | Drum | 58 | 7803 | |
871013743 | - | 1X800/35 | 1250 | Drum | 62 | 9300 | |
871014084 | - | 1X1000/35 | - | Drum | 67 | 11400 | |
* The values can have small deviations |