ALUflex ® XGLite - 0,6/1 kV

Application

ALUFLEX XGLite are used where halogen free cables are required for supplying electrical panels, machinery, industry, large building complexes, data centers or at the local electricity supply. The cables are suitable for burial and can be laid outdoor.

ALUflex® XGLite is registered in the database for construction products that can be used in the Nordic Ecolabelled (Svanen) construction.

Construction

Conductor

≤ 25 mm² round massive, class 1
≥ 50 mm² sector shaped multithreaded, class 2
*Sector shaped massive, class 1

Insulation

XLPE

Conductor color

Blue, brown, black, grey, (G=green/yellow conductor)

Inner sheath

Halogen free compound

Outer sheath

Halogen free compound, grey, meter marked

Technical data

Working temperature

+90° C

Rated voltage

0.6/1 kV

Test voltage

4 kV / 50 Hz

Bend radius

12 x cable diameter

Technical comments

Tensile load: up to 30 N/mm2
Resistance
*Please ask if Cca is required

CPR classification:

Cca-s1,d2,a1 / Eca

Please request for DoP at dop@scankab.dk

Approvals

EN 50575, IEC 60332-1, IEC 60502, IEC 60754, IEC 61034, HD 604-SF, HD 603-5G, CE, RoHS
Bending radius 12 x cable diameter
Can be buried
Can lay in tubes
Environmentally friendly
Flame retardant acc. to IEC 60332-1
For industrial use
For permanent outdoor installation
For use in cable trays
For use in homes
For use in switchboards
Halogen free
Low emission of corrosive gases acc. to IEC 60754
Low smoke emission during fire acc. to 61034
Max. working temp. +90° C
Meter marked
Outdoor use
Suitable for bricking
UV-resistant
SKU EAN CPR Dimension (mm2) Current Value (A) Winding Diameter (mm)* Weight (kg/km)*
131124003 5704403211340 Dca 3x240 427 D./Cut 45,6 2854
131101604M 5704403181919 Cca-s1,d2,a1 4x16 92 D./Cut 16,0 749
131102504M 5704403181933 Cca-s1,d2,a1 4x25 112 D./Cut 20,5 1245
131105004D 5704403210961 Dca 4x50 158 D./Cut 29,0 770
131109504D 5704403210978 Dca 4x95 234 D./Cut 34,5 1480
131109504M 5704403156597 Eca 4x95* 234 D./Cut 34,0 1480
131115004 5704403152940 Eca 4x150 300 D./Cut 42,5 2280
131115004D 5704403210985 Dca 4x150 300 D./Cut 42,5 2280
131118504 5704403193394 Eca 4x185 330 D./Cut 47,5 2850
131124004D 5704403208968 Dca 4x240 398 D./Cut 53,1 3620
131101605MG 5704403181926 Cca-s1,d2,a1 5G16 - D./Cut 20,0 390
131102505MG 5704403181940 Eca 5G25 102 D./Cut 24,0 580
131105005 5704403190027 Eca 5G50 158 D./Cut 33,5 962
* The values can have small deviations